H07RN-F - Heavy Duty Rubber Sheathed Cable
KIT CONTAIN:
CONDUCTOR | Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228 |
OUTER SHEATH | Flexible rubber. Black color. |
INSULATION | Rubber (type EPR). |
The standard identification of insulated conductors is the following: 1x Natural 2x Brown + Blue 3G Brown + Blue + Yellow/Green 4G Brown + Black + Grey + Yellow/Green 5G Brown + Black + Grey + Blue + Yellow/Green 6G Black numbered + Yellow/Green Or more |
- Maximum conductor operating temperature: +90°C ❊
- Maximum conductor temperature during short circuit: +250°C
- Lowest ambient temperature for fixed installation: -40°C
- Lowest ambient temperature for mobile installation: -25°C
- UV, sunlight, water, oil, abrasion resistant
- -25 meter submersible underwater ❊ Max continuous operating conductor temperature in normal use:
+60°C ( in every case of mobile installation )
+90°C ( fixed protected installation )
Conductors | Annealed flexible stranded bare copper or tinned copper, class 5 to EN 60228 |
Insulation | Ethylene-propylene rubber ( EPR) type EI4 in according to EN 50363-1 |
Filler | Rubber Strip with Cotton Rope as a filler will be applied between insulated conductors for sizes |
Separator | A non-woven separator will be applied between insulated conductor & jacket for size ≥10mm2 |
Jacket | Black, Chlorinated Polyethylene rubber ( CPE) EM2 in according to EN 50363-2-1 |
Flammability | EN 60332-1-2: 2004, IEC 60332-1-2: 2004 |
Reference | EN 60228, EN 50363-1, EN 50363-2-1, EN 60332-1-2, IEC 60332-1-2, DIN EN 50525-2-21, , DIN |
Approval | VDE, BS 6195 21150 0.6/1 KV IEC 60092-353 |
Circuit | Number | of Core G (earth core) | X (without earth core) |
2 | Blue, brown | 5Blue, brown | |
3 | Green/yellow, blue, brown | Brown, black, grey | |
4 | Green/yellow, brown, black, grey | Blue, brown, black, grey, black | |
5 | Green/yellow, blue, brown, black, grey | Blue, brown, black, grey, black | |
6 & above | Green/yellow, other cores | Black with white numbering |
Minimum bending radius | For cable diameter D (mm) | |||
D≤8 | 8<D≤12 | 12<D≤20 | D>12 | |
Fixed installation | 3 D | 3 D | 4 D | 4 D |
At inlet of portable appliance or mobile equipment, | 4 D | 4 D | 5 D | 6 D |
Under mechanical load | 6 D | 4 D | 5 D | 8 D |