Brass cable glands for single wire armour cable, indoor and out. Four types, BW, CW, E1W and A2, designed to BS 6121, each with its locknut, shroud and earth tag.
- Types
- BW, CW, E1W, A2
- Entry thread
- 20 to 90 mm
- Cable
- SWA
- Design
- BS 6121
Entry threads from 20 mm to 90 mm, for armoured and unarmoured cable. Open a gland for its photos and every size.

Raiden brass cable gland
CW Cable Gland
A brass indoor and outdoor gland for all single wire armour (SWA) cable, giving mechanical cable retention and electrical continuity through the armour wire termination. The clamping ring lets the cable be disconnected from the equipment for maintenance, and allows remote make-off where access is restricted. Designed and tested to BS 6121: Part 1: 1989; meets EN 50262:1999.
- Entry thread
- 20 to 90 mm
- Sizes
- 15
- Use
- Indoor and outdoor
- Ingress
- IP54
- Armour
- Cable outer sheath
Full specification
- Type
- CW
- Design
- BS 6121: Part 1: 1989
- Ingress protection
- IP54
- Material
- Brass (nickel-plated brass optional)
- Cable
- Single wire armour (SWA)
- Armour clamping
- Cable outer sheath
- Accessories
- Steel or brass locknut, PVC or LSF shroud, brass earth tag, nylon washer
| Size | Entry thread Ø C | Length E min | Inner sheath Ø A | Outer sheath Ø B | Armour Ø | Across flats D | Across corners |
|---|---|---|---|---|---|---|---|
| 20 S | 20 | 10 | 11.60 max | 16.00 max | 0.90/1.25 | 22.00 | 25.00 |
| 20 L | 20 | 10 | 14.50 max | 20.50 max | 0.90/1.25 | 25.40 | 28.50 |
| 25 S | 25 | 10 | 19.00 max | 24.00 max | 1.25/1.60 | 31.50 | 35.50 |
| 25 L | 25 | 10 | 20.50 max | 27.00 max | 1.25/1.60 | 33.00 | 37.00 |
| 32 S | 32 | 10 | 24.00 max | 30.50 max | 1.60/2.00 | 38.50 | 43.50 |
| 32 L | 32 | 10 | 27.00 max | 33.00 max | 1.60/2.00 | 41.00 | 46.50 |
| 40 S | 40 | 15 | 30.00 max | 37.00 max | 1.60/2.00 | 46.00 | 51.00 |
| 40 L | 40 | 15 | 33.50 max | 41.00 max | 1.60/2.00 | 48.50 | 55.00 |
| 50 S | 50 | 15 | 40.00 max | 47.00 max | 2.00/2.50 | 57.00 | 64.00 |
| 50 L | 50 | 15 | 44.00 max | 52.60 max | 2.00/2.50 | 61.00 | 68.00 |
| 63 S | 63 | 15 | 50.50 max | 60.00 max | 2.50 | 70.00 | 79.00 |
| 63 L | 63 | 15 | 56.00 max | 66.00 max | 2.50 | 78.00 | 86.00 |
| 75 S | 75 | 15 | 62.00 max | 72.00 max | 2.50 | 84.00 | 95.00 |
| 75 L | 75 | 15 | 68.00 max | 78.00 max | 2.50 | 92.00 | 102.00 |
| 90 L | 90 | 20 | 79.00 max | 90.00 max | 2.50/3.15 | 105.00 | 118.00 |
All sizes in mm.
- Gland
- Locknut
- Shroud
- Earth tag
- Up to 32 mm and 40 mm sizes
Four types at a glance. Open one for its photos and every size.
| Gland | ||||
|---|---|---|---|---|
| Use | Indoor | Indoor and outdoor | Indoor and outdoor | Indoor |
| Cable | SWA | SWA | SWA | Unarmoured |
| Armour clamping | Clamping ring | Cable outer sheath | Detachable cone and ring | Clamping ring (accessory) |
| Sealing | - | - | Cable outer sheath | Cable outer sheath |
| Ingress protection | - | IP54 | IP54 | IP66 |
| Entry threads | 20 to 75 mm | 20 to 90 mm | 20 to 75 mm | 20 to 75 mm |
| Sizes | 12 | 15 | 14 | 14 |
| Design | BS 6121: Part 1: 1989, meets EN 50262:1999 | |||
| Material | Brass, nickel-plated brass optional | |||
| Kit | Gland, locknut, shroud, earth tag | |||